| Type | Items | Specification |
| Capacity | Power rating | 30 kVA/30 kW |
| Input | Topology | PWM, IGBT based |
| | Rated voltage | 230/400Vac nominal (220/380,240/415 Selectable) |
| | Voltage range | -50% ~ +20%, depends on load percentage |
| | Input power factor | 0.99 |
| | THD(i) | <3% |
| | Rated Frequency | 50/60Hz auto sensing |
| | Frequency range | 42-72Hz |
| Output | Output Transformer | Default |
| | Power factor | 1 |
| | Efficiency | Up to 96% in online mode;>99% in ECO mode |
| | Voltage | 230/400Vac nominal(220/380, 240/415 Selectable) |
| | Frequency | 50/60Hz |
| | Overload capacity | 20KS-80KS model: 102110% load 60 min, 111125% load 10min, 126150% load 1min, >150% load 150msec
*20-80K battery kit model and STD internal battery model: depends on battery configuration. |
| | THDV | <2% for Linear load |
| | Unbalanced load | 100% |
| | Crest factor | 3:1 |
| Bypass | Internal static switch | Standard |
| | Bypass voltage | 400Vac(+/-15%) |
| | Maintenance bypass switch | Standard |
| Battery | Battery type | 20KS-80KS model: VRLA/NiCd/Lithium. 20-80K battery kit model and STD internal battery model: VRLA. |
| | Backup time | 20KS-80KS model: Varies from battery capacity and load situation. 20-80K battery kit model: Depends on battery configuration. 20-80K STD internal battery model: 3.5mins @ 100% load |
| | Battery PCS | 20KS-80KS model: depends on battery configuration. 20-80K battery kit model: 20-40K: up to 2*40 7Ah/9Ah max 60-80K: up to 4*40 7Ah/9Ah max 20-80K STD internal battery model: 20K: 1*40*9Ah 30K: 2*32*9Ah 40K : 2*40*9Ah 60K: 3*40*9Ah 80K: 4*40*9Ah |
| | Charger current | 20A/30A/40A/60A/80A max. |
| | Battery Voltage | 20KS-80KS model and 20-80K battery kit model: 432VDC default, 320V-607V 20-80K STD internal battery model: depends on internal battery. |
| | Recharge time | 8 hours to 90% |
| Dimension | WxDxH (mm) | 20KS-80KS model: 20-40KS 330*699*521mm; 60-80KS 331*773*972mm 20-80K battery kit model and STD internal battery model: 20-40K 500*859*887mm; 60-80K 500*859*1870mm (TBD) |
| Environment | Running temperature | UPS:0-40 C; Battery: 25 C |
| | Storage | -25~55 C without battery; +15~25 C with battery |
| | Humidity | 5%~95% |
| | Elevation | No reating <2000m |
| | Noise level | <= 65 dBA at1 m @75% Load (ISO7779) |
| Communication | Interface | 2xMini-Slot, 1xEmergency Power Off input(NC or NO),3xBuilding Alarm Inputs,1xRS232 |
| | Com cards(optional) | NMC & CMC cards, Relay card, EMP |
| International Standard | Safety | IEC/EN 62040-1 |
| | EMC | IEC/EN 62040-2 |
| | Performance | IEC/EN 62040-3 |
| | Quality | ISO9001,ISO14001 |
| | Certification | CE |