| Type | Items | Specification |
| Capacity | Output power | 10 kVA / 8 kW |
| Input | Number of phases | 3Ph+N+PE |
| | Nominal Voltage | 380V (Ph-Ph) |
| | Voltage range (100% load) (Ph-N) | (-15)% (+27)% |
| | Voltage range (64% load) (Ph-N) | (-45)% (+27)% |
| | Voltage range (42% load) (Ph-N) | (-64)% (+27)% |
| | Nominal Frequency (Hz) | 50 |
| | Frequency range | +/-10% |
| | Input Current THD | <= 4% |
| | Input Power Factor | 0.99 |
| Output | Number of phases | 3Ph+N+PE |
| | Voltage | 380V (Ph-Ph) |
| | Voltage Regulation at 100% linear load (online&bat | < 1% |
| | Voltage THD at rated linear load | < 3% |
| | Crest factor | 3:1 |
| | Frequency (Hz) | 50 |
| | Free Running Frequency (Hz) | +/- 0.01% |
| Overload Rating | Overload | 125% for 10 minutes, 150% for 1 minute |
| Efficiency | Efficiency | 92% |
| Static Bypass Line | Number of phases | 3Ph+N+PE |
| | Voltage range for bypass operation | 220V (Ph-N) +/- 10% |
| | Frequency range for bypass operation (Hz) | 47-53 (Configurable) |
| Battery | Type | Seal Lead Acid Maintenace Free |
| | Battery Quantity | 62 (2*31) |
| | Battery Protection | Deep Discharge Protection with Auto Cut off |
| | Battery Test | Standard (Automatic and Manual) |
| Indicator | LCD | Load%, Input&Output Frequency, Voltage&Current, Bypass voltage, Battery Voltage & current, Temperature, Alarms |
| Dimension | Dimensions WxDxH (cm) | 40 x 78 x 107 |
| Weight | Weight (kg) | 102 |
| Environment | Storage Temperature Range (C) | -25 to +55 |
| | Operation Temperature (C) | 0 to 40 |
| | Relative Humidity Range | 0-95% (non-condensing) |
| | Maximum Altitude without derating (m) | 1000 |
| | Protection Level | IP20 |
| | Noise Level | <60 dB |
| Communication | Interface | RS232 & RS422 |
| | Dry Contact Signals | AC failure,Battery under voltage,Bypass,Output failure |
| | Others | EPO,Generator interface |
| International Standard | Standard | EN50091-1-1,EN50091-2,EN50091-3,EN55022,EN62040-1-1,EN62040-2,EN62040-3 (VFI-SS-111) |
| | Product Certification | CE |